8610 Production Avenue l San Diego, California 92121 l (858) 566-7465 l Fax (858) 566-1943WKE SERIES(USA ONLY)--INSTALLATION INSTRUCTIONS--Thank yo
WKE03/02 PG 2INSTALLATION INSTRUCTIONSFOR WKE SERIES SENTINEL II EQUIPPED COOLING UNITS The BREEZAIRE WKE Series cooling units are designed to, when
WKE03/02 PG 3 If your installation cannot be performed in accordance with these instructions contact your dealer. The unit must be installed in the
WKE03/02 PG 4from condensing on the cold surface of the cooling unit in the wall. Please remember that in all cases the warm airexhaust grille must b
WKE03/02 PG 5Should the cooling system be suspected of malfunctioning, check the temperature of the air being exhausted from theupper part of the warm
WKE03/02 PG 6SENTINEL II CONTROL SYSTEM The BREEZAIRE Sentinel II is the precision micro-processor control system that makes the WKE Series the mosts
WKE03/02 PG 7 When the cooling unit is plugged in and receiving electrical power the top arrow will be lit. This top arrow will blinkwhen the compre